A drone carrying both a visual (RGB) camera and a radiometric thermal camera captures two views of the same pole. Visual images show physical condition; thermal images show components that may be running hotter than they should. Every finding is flagged for confirmation by qualified line crews.
1. Connectors and splices
- Visual: loose or displaced hardware, corrosion, broken or bird-caged strands.
- Thermal: warmer spots that may indicate high resistance from looseness or corrosion.
2. Fuse cutouts and switches
- Visual: cracked barrels, misaligned blades, tracking marks.
- Thermal: heating at hinge or clip contacts, which may point to loose or corroded contacts.
3. Pole-mounted transformers
- Visual: oil stains or leaks, chipped bushings, rust on the tank.
- Thermal: heating at bushing connections. Unusual heat patterns on the tank are flagged for follow-up, and the oil level can sometimes be seen as a temperature boundary.
4. Surge arresters
- Visual: cracks, separated ground-lead disconnectors, contamination.
- Thermal: an arrester warmer than its neighbours under normal voltage may indicate internal deterioration and should be checked promptly.
5. Insulators
- Visual: chips, cracks, contamination, tracking marks, damaged tie wires.
- Thermal: heating along the surface that may indicate leakage current.
6. Crossarms and hardware
- Visual: splits, rot, bent braces, loose bolts.
- Thermal: leakage current from a failing insulator into a wood crossarm heats the wood, and in some cases can start a pole-top fire.